Project Description: Knine demoed old Inovonics Wireless Receiver as defined by drawings provided by Advance Alarms.
Project Description: Knine demoed old Inovonics Wireless Receiver as defined by drawings provided by Advance Alarms.
Service Ticket #3058 performed on 7/10/24 Technician arrived onsite and found the issues the site was having were with the Fire Alarm Panel. After troubleshooting the Technician found that water was getting into the Fire Alarm Booster Panel and the Ceiling Mount Strobe was full of water. This was what was causing the trouble to come in and out. The site was going to check and see if they could find where the water was coming from but for now the the Technician put silicon in the conduits that come down into the Booster Panel. Technician also fixed 7 blurry cameras and the site had 2 cameras that were dead that will need to be replaced at 5211 building. (tank farm view 5, flammable cylinder holding area). The site was ok with not replacing the 2 bad cameras. There are other cameras viewing the same thing.
Project Description: K9AS installed the QT PPD Hardware and cabling according to drawings provided by Advanced Alarms.
Technician arrived onsite to check out the Security System. Technician went through the Zones on the Panel and then checked out all the Zones. After going through all the Zones, the Technician got the Panel to go normal when all the doors were closed for a short moment as the motions kept getting tripped by workers in the Shop Area. Technician labeled the Zones on the drawing for the site. Technician also told the site to double check that the doors were closed as well if the Zones still showed open.
Technician arrived onsite and replaced the Roll Up Door 9 Contact. Technician checked the system and the system was clear and working properly upon completion.
Technician arrived onsite and checked out the Security System. All the Zones were working properly. Most of the doors, had to be checked that they were shutting all the way but once they were shut the system would go to Readyto-Arm. System had a low system Battery, so the Technician replaced the Battery with one 12V 7AH Battery. Customer was not able to get into Camera System to make any changes. Per sites request a quote to upgrade the cameras to IP Cameras will be provided.
Technician arrived onsite and installed the new PPD station and tested with support. Everything is working perfectly as it should.
Technician replaced 2 outdoor cameras, 1 bullet and 1 LPR on the Olympic facility. Technician ran cabling to add two additional outdoor bullet cameras covering the Industrial facility far right corner at the end of the docks.
Technician arrived and was able to find the cause of the .6v which is Zone 2 it goes back to the S2 panel in the IT room on a relay. When removed the panel reads 1v between terminal 12 and 30 which is good. Swapped strands to green and white put them back on zone 2 which made it read .6v which is ok. Checked the Riser number 4 which was the one saying low pressure, made sure all connections and covers were seated properly. Checked for any exposed wire. The ground faults are read the V128-FBT panel.
Technician arrived at store 1702 UPS is now online. EXT 5 is now reachable EXT 1,6,9,11 was cleaned All but EXT 5 had packet issue resolved EXT 5 has a altronix 4 port netway on the base of pole possible bad already has 1 bad port labeled
Site called requesting a technician to come out due to ground fault error has returned. Technician called resideo Honeywell tech support and was told that .6v is ok between terminal 12 and 30 because it was within .5v of 1v. If it still keeps getting ground faults to unwire everything but the power and a keypad and check again. If they keep coming to remove the panel from the can and check again. At that point if the panel has not stop giving ground faults to replace the panel. The technician looked at all the zones and the polling loop to verify correct voltage and we’re all reading .6v. Before leaving there was no fault on keypad, and everything was normal.
Site called requesting for a technician to come out to due to some cameras not recording. Technician went through and double checked all the cameras again to make sure the motion was turned on inside the camera itself and set motion areas on ones that he found that we're not set yet. All cameras are recording now properly.
Site requested for a technician to come out for the memory care door keypad was not working properly. The technician found that the circuit board was getting pinched between the keypad and the cut in box. The technician trimmed out the edges of the cut in box to where the keypad would fit better remounted and tested about 40 times with no issues.
Technician troubleshooted/repaired Relay/Sounder and Alarm Contacts.
Technician troubleshooted/repaired Relay/Sounder and Alarm Contacts.
Technician troubleshooted/repaired Relay/Sounder and Alarm Contacts.
Technician was requested to check keypad that was not working. The technician opened the keypad up and the negative wire was broke was able to repair the wire. When the technician was putting the keypad back together, he noticed that the top clips were all broken off, so it will not stay completely latched anymore. Site told the technician they will request for a new one within a few months.
Knine replaced two Avigilon systems in each building with one Exacq server capable of handling all cameras in the building. Knine moved all working cameras to the new unit and if any cameras that was not working, we troubleshooted/repaired.
Knine replaced two Avigilon systems in each building with one Exacq server capable of handling all camera in the building. Knine removed all working cameras to the new unit and troubleshooted any cameras that was not working properly.
The site had 20+ cameras down we were able to get servers 1 and 2 back online but server 3 will not connect. Server 3 needs a new hard drive we will get that ordered and return to site once the part arrives.
We replaced an access control keypad on one of the memory care doors that was malfunctioning.